The 48000 BTU Under/Floor Ceiling Split from Green Air-Conditioning is best suited for home, office and industrial use. This aircon will work optimal in rooms and areas with a floor size of up to 80m². Our franchises, agents and dealers are all highly trained professionals and will also be able to assist you with the installation.
Feel free to request a quote or contact us for expert advise.
Type of Unit | UNDER/FLOOR CEILING | ||
---|---|---|---|
Model | UFCM-H48 | ||
Indoor Power Supply | V~,Hz,Ph | 220~240/50/1 | |
Cooling | Capacity | Btu/h | 48000 |
kW | 14.07 | ||
Input | kW | 4.85 | |
Rated current | A | 9.10 | |
EER | W/W | 2.90 | |
Heating | Capacity | Btu/h | 53057 |
Kw | 15.55 | ||
Input | kW | 4.8 | |
Rated current | A | 9 | |
COP | w/w | 3.24 | |
Indoor Fan Motor | Model |
FP140F |
|
Output Power x Fan Quantity | W | 140 x 1 | |
Capacitor | uF | 8.0 | |
Speed (Hi/Med/Low) | r/min | 1310/1050/860 | |
Indoor Coil | Number of Rows | 3 | |
Tube Pitch (a) x Row Pitch (b) | mm | 20.5 x 12.7 | |
Fin Pitch | mm | 1.5 | |
Fin Type | Hydrophilic | ||
Tube Outside Dia. and Type | mm | 7 Inner grooved | |
Coil length x height x width | mm | 1291 x 307 x 38.1 | |
Number of Circuits | 7 | ||
Indoor Airflow (Hi/Mi/Lo) | m³/h | 2000/1800/1250 | |
Indoor noise level (Hi/Mi/Lo) | dB(A) | 51/46/40 | |
Indoor Unit | Dimension (W x D x H) | mm | 1600 x 235 x 690 |
Packaging (W x D x H) | mm | 1680 x 325 x 770 | |
Net/Gross weight | Kg | 44/50.5 | |
Wired Controller | YKR-T/021E | ||
Outdoor Power Supply | V~,Hz,Ph | 380~415/50/3 | |
Max Input Consumption | W | 6800 | |
Compressor | Model | GTE498UC3Q9PK1 | |
Type | Twin Rotary | ||
Brand | Highly | ||
Capacity | W | 12650 | |
Input | W | 4130 | |
Rated current (RLA) | A | 7.2 | |
Locked rotor (LRA) | A | 69 | |
Thermal protector Temp. | 165 | ||
Capacitor | uF | / | |
Refrigerant Oil | ml | 1600 | |
Outdoor Motor Fan | Model | CW60A | |
Output Power x Fan Quantity | W | 60 x 2 | |
Capacitor | uF | 3.5*2 | |
Speed | r/min | 750 | |
Outdoor Coil | Number of rows | 1.5 | |
Tube Pitch (a) x Row Pitch (b) | mm | 22 x 19.05 | |
Fin spacing | mm | 1.6 | |
Fin type | Hydrophilic aluminum | ||
Tube outside dia. and type | mm | 7 Inner grooved | |
Coil length x height x width | mm | (918+530) x 1276 x 38.1 | |
Number of circuits | 9 | ||
Outdoor Airflow Volume | m³h / CFM | 5800 / 3412 | |
Outdoor noise level | dB(A) | 60 | |
Outdoor Unit | Dimension (W x D x H) | mm | 940 x 370 x 1325 |
Packaging (W x D x H) | mm | 1080 x 430 x 1440 | |
Net/Gross weight | Kg | 95/105 | |
Refrigerant | Type/Quantity | g | R410a/3000 |
Design Pressure | MPa | 4.4/1.4 | |
Connecting Wiring | Power Wiring (Indoor) | mm² | 3 x 1 |
Power wiring (Outdoor) | mm² | 5 x 4 | |
Signal wiring | mm² | 2 × 1 | |
Refrigerant Piping | Liquid Side / Gas Side | mm | 9.52/19.05 (3/8 x 3/4) |
Max Pipe Length | m | 50 | |
Max High Drop | m | 30 | |
Ambient Temp | Cooling | °C | -5~49 |
Heating | °C | -15~24 |