The 60000 BTU Ducted Split from Green Air-Conditioning is best suited for office and industrial use. This aircon will work optimal in rooms and areas with a floor size of up to 100m². Our franchises, agents and dealers are all highly trained professionals and will also be able to assist you with the installation.
Feel free to request a quote or contact us for expert advise.
Type of Unit | DUCTED SPLIT | ||
---|---|---|---|
Model | DUCM-H60 | ||
Indoor Power Supply | V-Ph-Hz | 220~240/1/50 | |
Cooling | Capacity | Btu/h | 60000 |
kW | 17.60 | ||
Input | kW | 6.26 | |
Rated current | A | 11.34 | |
EER | W/W | 2.60 | |
Heating | Capacity | Btu/h | 63500 |
Kw | 18.50 | ||
Input | kW | 5.78 | |
Rated current | A | 10.36 | |
COP | w/w | 3.20 | |
Indoor Fan Motor | Model |
FP240A |
|
Output Power x Fan Quantity | W | 240 x 1 | |
Capacitor | uF | 12 | |
Speed (Hi/Med/Low) | r/min | 1385/1240/1160 | |
Indoor Coil | Number of Rows | 3 | |
Tube Pitch (a) x Row Pitch (b) | mm | 20.5 x 12.7 | |
Fin Pitch | mm | 1.4 | |
Fin Type | Hydrophilic aluminum | ||
Tube Outside Dia. and Type | mm | 7 Inner grooved | |
Coil length x height x width | mm | 985 x 328 x 38.1 | |
Number of Circuits | 8 | ||
Indoor Airflow (Hi/Mi/Lo) | m³/h | 2600/2300/1950 | |
Indoor noise level (Hi/Mi/Lo) | dB(A) | 50/47/45 | |
Indoor Unit | Dimension (W x D x H) | mm | |
Packaging (W x D x H) | mm | ||
Net/Gross weight | Kg | 50/56 | |
External Static Pressure | Pa | 80 | |
Wireless Remote Controller | XK05-DY | ||
Outdoor Power Supply | V-Ph-Hz | 380~415/3/50 | |
Max Input Consumption | W | 7300 | |
Compressor | Model | ATE590SC3Q9JK | |
Type | Twin Rotary | ||
Brand | Highly | ||
Capacity | W | 14850 | |
Input | W | 4950 | |
Rated current (RLA) | A | 8.7 | |
Locked rotor (LRA) | A | 65 | |
Thermal protector Temp. | 165 | ||
Capacitor | uF | / | |
Refrigerant Oil | ml | 1850 | |
Outdoor Motor Fan | Model | CW60A | |
Output Power x Fan Quantity | W | 60 x 2 | |
Capacitor | uF | 3.5*2 | |
Speed | r/min | 750 | |
Outdoor Coil | Number of rows | 1.5 | |
Tube Pitch (a) x Row Pitch (b) | mm | 22 x 19.05 | |
Fin spacing | mm | 1.6 | |
Fin type | Hydrophilic aluminum | ||
Tube outside dia. and type | mm | 7 Inner grooved | |
Coil length x height x width | mm | (918+530) x 1276 x 38.1 | |
Number of circuits | 9 | ||
Outdoor Airflow Volume | m³h / CFM | 5800 / 3412 | |
Outdoor noise level | dB(A) | 60 | |
Outdoor Unit | Dimension (W x D x H) | mm | 940 x 370 x 1325 |
Packaging (W x D x H) | mm | 1080 x 430 x 1440 | |
Net/Gross weight | Kg | 99/109 | |
Refrigerant | Type/Quantity | g | R410a/3000 |
Design Pressure | MPa | 4.4/1.4 | |
Connecting Wiring | Power Wiring (Indoor) | mm² | 3 x 1 |
Power wiring (Outdoor) | mm² | 5 x 4 | |
Signal wiring | mm² | 2 × 1 | |
Refrigerant Piping | Liquid Side / Gas Side | mm | 9.52/19.05 (3/8 x 3/4) |
Max Pipe Length | m | 50 | |
Max High Drop | m | 30 | |
Ambient Temp | Cooling | °C | -5~49 |
Heating | °C | -15~24 | |
Ducting | Supply Air Size | mm | 975 x 190 |
Return Air Size | mm | 1185 x 300 |