The 60,000 BTU Inverter Ceiling Cassette from Green Air-Conditioning is best suited for home, office and industrial use. This energy-saving aircon will work optimal in rooms with a floor size of up to 100m². Our franchises, agents and dealers are all highly trained professionals and will also be able to assist you with the installation.
Feel free to request a quote or contact us for expert advise.
Indoor Model | CM-C60UNI-I | ||
Panel | PE-QFA/CD | ||
Electric Parameter | |||
Power Supply | Indoor | V-ph-Hz | 220-240/1/50 |
Outdoor | V-ph-Hz | 380-415/3/50 | |
Input Consumption | Max | W | 7,800 |
Input Current | Max | A | 13.8 |
Cooling | |||
Capacity | Nominal | Btu/h | 52,886 |
W | 15,500 | ||
Min - Max | W | 4,800 - 16,200 | |
Input | Nominal | W | 6,460 |
Current | A | 10.9 | |
EER | W/W | 2.40 | |
Heating | |||
Capacity | Nominal | Btu/h | 52,886 |
W | 15,500 | ||
Min - Max | W | 3,600 - 17,200 | |
Input | Nominal | W | 4,920 |
Current | A | 8.3 | |
COP | W/W | 3.15 | |
Indoor Fan Motor | |||
Model | ZW511B500062 | ||
Quantity | 1 | ||
Output | W | 101 | |
Capacitor | μF | - | |
Speed (Hi / Medium / Low) | r/min | 780 / 700 / 640 | |
Indoor Coil | |||
Number of Rows | 3 | ||
Tube Pitch (a) x Row Pitch (b) | mm | 21 x 13.6 | |
Fin Spacing | mm | 1.5 | |
Fin Type | Hydrophilic Aluminium | ||
Tube Outside Diameter & Type | mm | Φ7, Innergroove Tube | |
Coil Length x Height x Width | mm | 2,096 x 231 x 40.8 | |
Number of Circuits | 5 | ||
Indoor Unit | |||
Dimension | W x H x D | mm | 840 x 272 x 840 |
Packaging | W x H x D | mm | 950 x 360 x 950 |
Weight | Net / Gross | kg | 26.0 / 32 |
Air Volume | Hi / Medium / Low | m³/h | 2,100 / 1,900 / 1,700 |
CFM | 1,236 / 1,118 / 1,001 | ||
Sound Level (SPL) | db(A) | 56 / 54 / 52 | |
Sound Level (PWL) | Hi | db(A) | 65 |
External Static Pressure | Rated | Pa | NA |
Before Shipment | Pa | NA | |
Range | Pa | NA | |
Controller | Type | Wireless | |
Model |
R2-01 (E) (Standard) J1-06 (E) (Optional) L1-12 (E) (Optional) RCH-RVD01 (Optional) YXE-E01U (E) (Optional) YXE-E02U (E) (Optional) YXE-C01U1 (E) (Optional) |
||
Drainage Water Pipe Diameter | mm | ODΦ32 | |
Drain Pump | Standard | ||
Air Filter | Standard | ||
Throttle Type | NA | ||
Booster Heater | kW | NA | |
Design Pressure | H/L | MPa | 4.15 / 1.6 |
Panel | |||
Dimension | W x H x D | mm | 950 x 50 x 950 |
Packing | W x H x D | mm | 1,020 x 1,000 x 105 |
Weight | Net / Gross | kg | 6.5 / 9 |
Room Temperature | |||
Setting Temperature Range | Cooling | ℃ | 16~30 |
Heating | ℃ | 16~30 | |
Outdoor Model | CM-C60UNI-O | ||
Compressor | |||
Model | WHP15600GUKPC8DQC | ||
Type | Rotary | ||
Brand | Highly | ||
Capacity | Btu/h | 40,262 | |
Input | W | 3,580 | |
Rated Current (RLA) | A | 15.8 | |
Refigerant Oil | Model | RmM68EA | |
Amount | ml | 1,050 | |
Outdoor Fan Motor | |||
Model |
ZW511A800002 ZW511A800052 |
||
Quantity | 2 | ||
Output | W | 60 | |
Capacitor | μF | / | |
Speed | r/min | 880 | |
Outdoor Coil | |||
Number of Rows | 2 | ||
Tube Pitch (a) x Row Pitch (b) | mm | 21 x 21.65 | |
Fin Spacing | mm | 1.5 | |
Fin Type | Hydrophilic Aluminium | ||
Tube Outside Diameter & Type | mm | Φ7.94, Innergroove Tube | |
Coil Length x Height x Width | mm | 881 x 1,134 x 64.95 | |
Number of Circuits | 8 | ||
Outdoor Unit | |||
Dimension | W x H x D | mm | 900 x 1,170 x 320 |
Packaging | W x H x D | mm | 970 x 1,300 x 430 |
Weight | Net / Gross | kg | 86.5 / 95 |
Air Volume | Hi | m³/h | 5,500 |
Sound Level (SPL) | db(A) | 59 | |
Sound Level (PWL) | db(A) | 72 | |
Refrigerant | Type | R410A | |
Amount | kg | 4.00 | |
TCO2Eq | 8.352 | ||
GWP | 2,088 | ||
Throttle Type | EEV | ||
Design Pressure | H/L | MPa | 4.15 / 1.6 |
Refrigerant Piping | |||
Liquid / Gas | mm (inch) | Φ9.52 / Φ19.05 (3/8" / 3/4") | |
Pipe Length | Max | m | 50 |
Height Difference | Max (OD Lower) | m | 30 |
Max (OD Heigher) | m | 30 | |
ADD Refrigerant Amount | g/m | 35 | |
Pipe Length For Additional Refrigerant | m | 5 | |
Operating Range | |||
Cooling | ℃ | -15~48 | |
Heating | ℃ | -10~24 |